Monday, January 20, 2014

Calculation of ventilation in short




Note this page can also be translated to Arabic , urdu etc                                                                

Air exchange area and calculation of fans in a poultry house

Air exchange area  m3/minute = Length width height
For example
Air exchange area m3/minute =  120m×12m×03m =4320m3

Air exchange area m3/minute =  4320 m3


No. of fan needed for air exchange  =

 Air volume m3/minute   Air exchange capacity of Fan
Standards  
                    1. Fan with a diameter of 1.2m      = 566 m3/minute  
                    2. Fan with a diameter of 1.0m      = 283 m3/minute  
                    3. Fan with a diameter of 91cm     = 255 m3/minute  

For example

No. of fan needed for air exchange = Air volume m3/minute ÷ Air exchange capacity of Fan

No. of fan needed for air exchange =  4320 ÷ 566 =7.6 or 8 Fans

No. of fan needed for air exchange = 08 fans

                                                                                                                                                               
                                                                                                                                                               


Calculation of space for Cooling Pad in poultry house(m2) =

(Fan air exchange Capacity m3/minute × Number of fans)÷ AirSpeed through cooling pad m3/minute

Standards

    3. For 100mm (10cm or 4-in) thick Pad,
                                                                use     ( 1.27m/s  or 76m/minute )(250fpm)

    4. For 150mm (15cm or 6-in) thick Pad, 
                                                                use   ( 1.91m/s or  114/minute ) (375fpm)

For example
Cooling  Pad area m2
= (Fan air exchange Capacity m3/minute × No. of fans)÷ (Air Speed through cooling pad m3/minute)

Cooling  Pad area = (566  × 8 )÷114 = 39.7mOr  40m2

*It means  20m2 (2m in width and 10 m in length) on each side of the house

Cooling  Pad area in m2 = 40m2







The number of fans Needed to exchange required air velocity

=(Required Air velocity m/s  ) ÷{  Fan capacity ÷ (width × Height ×60) }

Standard  Air velocity

Rearing      ˃ 2.03 meters per second (m/s) OR 400 Feet per minute (fpm)
Production ˃ 2.54 meters per second (m/s) OR 500 Feet per minute (fpm)

For example

The number of fans Needed to exchange required air velocity 
(Required Air velocity m/s  ) ÷{  Fan capacity ÷ (width × Height ×60) }

No. of fans Needed to exchange required air velocity  =(2.03) ÷ { 566 ÷(12×03×60} =7.8 fans


No. of fans Needed to exchange required air velocity  = Fans 8


Minimum Ventilation Calculation For Fan Timer Setting

Standards
Minimum ventilation per bird
Age
Cubic meter per hour
(CMH/Bird)
Cubic feet per minute
(CFM/Bird)
01-08 weeks
0.16
0.10
09-15 weeks
0.42
0.25
16-35 weeks
0.59
0.35
35- depletion
0.76
0.45



For example

Bird Age = 20 weeks
Number of Birds = 10,000
Minimum ventilation fan = 1 × 91 cm =255 m3/minute × 60 =( 15300m3/hr )
Using a 5 minutes cycle timer
Calculate the minimum Ventilation?

Step:1
 Ventilation rate = (Minimum ventilation per bird) ×( Number of Birds)
             Ventilation rate= (0.59 cmh) ×(10,000) = 5,900 cmh (cubic meter per hours)

Percentage time the fans needed to be run for

Step:2 
Percentage time = (Total ventilation needed) ÷ (Total capacity of fans used)
Percentage time =(5,900cmh) ÷ (15,300) =0.39 or 39%


Percentage time =39%

*It means if a 5-minute timer is used, the run timer required would be then 39% of  5 minutes or 117 seconds
( or the fan should be 24 sec on and 36 sec off for each minute)

                                                                                                                                                               


For example

Bird Age = 01 weeks
Number of Birds = 10,000
Minimum ventilation fan = 1 × 91 cm =255 m3/minute × 60 =( 15300m3/hr )
Using a 5 minutes cycle timer
Calculate the minimum Ventilation?

Step:1
 Ventilation rate = (Minimum ventilation per bird) ×( Number of Birds)
             Ventilation rate= (0.16 cmh) ×(10,000) = 1600 cmh (cubic meter per houre)

Percentage time the fans needed to be run for

Step:2 
Percentage time = (Total ventilation needed) ÷ (Total capacity of fans used)
Percentage time =(1600cmh) ÷ (15,300) =0.10 or 10%


Percentage time =10%

*Assuming a 05-minute cycle timer, the run Timer required would then be 10 % of 05 minutes or 30 seconds 
                                                                                                                                                               



Ventilation standers for Layers





36 comments:

Unknown said...

MA SHA ALLAH DR.SAHIB GOOD WORK, KEEP IT UP.

Poultry Breeders Management said...

THANKS DR. SAHIB

Dr.Habib-ur-Rehman said...

Realy good work for new commers.
VERY GOOD

Poultry Breeders Management said...

Thanks Sir,Dr.Habib-ur-Rehman for complements.

Unknown said...

excellent

Poultry Breeders Management said...

Thanks Respected Dr Majid Gilani sahib

Unknown said...

i didnt understand anything

Poultry Breeders Management said...

Read it again carefully

Poultry Breeders Management said...

Read it again carefully

Unknown said...

Very Good work
I have one question about the length of the cooling pad in each side of the house.
Do we have maximum or minimum length we have to follow ?
if the house is 100 meter long for example. Is there is a limitation of length of cooling pad ( not more than 30% of the house length ).
Thanks for your reply in advance.
Motasam Ezelarab, Egypt

imran panwala said...

masha ALLAH dr sahib can i have your contact no.

Poultry Breeders Management said...

thanks 00966500328111

Dr.Habib-ur-Rehman said...

What are the minimum ventilation rates for cage layer. If have any information box me.
dr.habib@gmail.com

seor1 said...

What are the minimum ventilation rates for cage layer. If have any information box me.
malik_naveed001@yahoo.com

seor1 said...

https://www.poultryventilation.com/sites/default/files/presentations/winnepeg.pdf

ssidana said...

Please give me in calculation of ventilation for Pullet and Layer Houses considering temperature of 45 degree Celsius. email address ssidana@mail.com

Poultry Breeders Management said...

Very strange question in modern poultry the normal temperature is 18-24 Celsius for Pullet and Layer.At 45 degree Celsius very hard for chicken to survive .

Unknown said...

how does the housing pressure affect in choosing Fan for poultry?
because at different pressure, we have different volume capacity?
i dont see any formula mentioning about noticing the pressure.
thanks very much

dvm nooralam fayzan from Afghanistan said...

I have only 4 question: how we can calculate fresh air for 1000 pullet in one hour? how much Co2 produced by 1000 layer in one hour? how much oxygen required for one layer in one hour? and how much Co2 can kill a layer? thank in advance

Unknown said...

this is my email address: nooralam.fayzan59@gmail.com

Unknown said...

Dr sahib i need calculation for open sided structure

Animate said...

A Very good clarification

Unknown said...

Very good work. Sir is there any information about broiler management if yess then please tell me the link. Thanx

Poultry Breeders Management said...

There is a broiler management guide. You can download it

Unknown said...

kindly share me the link for broiler management guide at drwaqas34@gmail.com

Unknown said...

Please send this me at my email address

Flowinsta said...

Sir how we calculate Cfm

Unknown said...

Sir ur id mail plz

Vijay Raj India Poultry Equipment's Manufacturer & Supplier said...

Nice Blog Thank you for Sharing information. For Poultry Environment Controller Equipment's in India visit Vijay Raj Poultry .

subhash said...

what is the standard requirement of layer breeder bird in hot weather in cfm/bird in possitive air pressure house.and how much possitive presser we mainten for good production

Unknown said...

Whewre you get yours below given values?
& What is this?
1. Fan with diameter of 1.2m = 566 m3/minute
2. Fan with diameter of 1.0m = 283 m3/minute
3. Fan with diameter of 91 cm= 255 m3/minute
Others things I have to understand but what is above valus
Kindly reply

Vijay Raj India Poultry Equipment's Manufacturer & Supplier said...

Nice Blog Thank you for sharing information about poultry products. To Buy Cooling Pads for Poultry Houses visit Vijay Raj Poultry Equipments Pvt Ltd.

Vijay Raj India Poultry Equipment's Manufacturer & Supplier said...

Thank you for sharing information about poultry maintenance in your blog. To Buy Poultry Environment Controller Equipment’s at Best Price in India Visit Vijay Raj Poultry Equipments Pvt Ltd.

Nadeem Aamir said...

excellent work

Anonymous said...

She is considering out side temperature

Poultry Breeders Management said...

thanks